The Institute for Physical Research and Technology's (IPRT) Facilities Engineering and Safety (FE&S) Group has developed procedures for ground-fault circuit-interrupters (GFCI) to help safeguard IPRT employees. Testing records have indicated a significant number of failures which demonstrate the clear need for testing. IPRT FE&S has decided to take a proactive stance to prevent injuries from occurring due to these failures by identifying and having faulty GFCI's repaired.
I. Personnel Responsibilities
II. Definition
Properly operating ground-fault circuit-interrupters (GFCI) will provide protection from electrocution of personnel in the event that the electrical ground is lost or an electrical leak occurs.
III. Location of GFCI's
IV. Installation of GFCI's
All newly constructed and renovated buildings will have the
required GFCI's installed. Other installations to retrofit receptacles with GFCI's are
only available through departmental or research funding.
GFCI's must be wired correctly to ensure that they will provide protection. A non-GFCI
receptacle can be wired downstream and in parallel with a GFCI to provide the same
protection. GFCI protection can also be obtained through a GFCI equipped circuit breaker
or extension cord.
V. Testing of GFCI's
IPRT FE&S will test all known IPRT (non-Ames Lab)
GFCI's and outlets with GFCI protection. Testing will occur upon installation, annually
and upon request. Any new GFCI, or non-stickered receptacle with GFCI protection, should
be reported to IPRT FE&S in room 101, ASC III (4-6812). An IPRT GFCI test sticker (see
appendix A) will be affixed to all GFCI's that meet the testing requirements. If the
outlet fails the testing procedures outlined in section VIII, a caution label (see
appendix B) will be placed over the outlet and repairs will be made as soon as possible.
The outlet shall NOT be used until repairs are made. IPRT FE&S will coordinate repairs
to faulty GFCI's through the IPRT Facilities Engineer.
Those persons using GFCI's should test them before each
use by pressing the test button on the outlet, checking to make sure it trips out, and
subsequently resetting it. (see section VII., A.) Do NOT use the outlet if it fails the
test. Report any problems to IPRT FE&S for correction. IPRT FE&S will maintain all
inspection records which will be available upon request.
VI. Acceptable Test Levels
In order for a GFCI to be in proper working order the circuit must be correctly wired and interrupt the circuit (trip) within 4 to 7 milliamperes (mA). A GFCI that trips at less than 4 mA is too sensitive and will cause unnecessary circuit interruptions. A GFCI that trips at greater than 7 mA will not provide the necessary personal protection to prevent possible electrocution.
VII. Documentation (IPRT FE&S)
A. Maps that indicate the locations of all GFCI's in IPRT-controlled spaces (see appendix C) shall be updated with the locations of all GFCI's.
B. GFCI test records that give the building, room number, outlet, circuit and breaker numbers, and the outlet type (see appendix D) shall be filled out as the testing is being done. The person performing the tests outlined in section VIII must fill out the date, their initials, the status of the push-button test, the wiring test and the GFCI circuit challenge, and shall indicate any problems with the outlet.
C. If the outlet fails any of the tests outlined in section VIII, a caution label (see appendix B) should be placed over the outlet. Fill out the caution label by indicating why the circuit is in need of repair and the test date. The reason for failure should also be documented on the GFCI test record (see appendix D). After repairs have been made to the outlet, it shall be re-tested to ensure it is in proper working condition.
D. Once the outlet has passed all the tests outlined
in section VIII, an IPRT GFCI test sticker (see appendix A) shall be placed on the outlet
cover. The test sticker shall indicate:
The test date,
VIII. Testing Procedures
To properly test all GFCI's, the energized circuit load must be able to be shut down. All equipment using that circuit would subsequently lose its source of energy. In cases where equipment cannot be shut down on demand, IPRT FE&S will coordinate a time when the GFCI testing can take place. All GFCI outlets and protected outlets will be tested individually to ensure they all meet protection requirements. A full GFCI test involves the Test/Reset Button Test, Wiring Test, and GFCI Circuit Challenge.
A. Test/Reset Button Test
Ensure the energized circuit can be appropriately
de-energized.
B. Wiring Test
Acquire an accepted wiring tester. (IPRT FE&S has
a Greenlee GFCI Circuit Tester with a wiring tester, Cat# 5708, NAED/DCI# 78-3310/34523.)
C. GFCI Circuit Challenge
d. If the circuit does not trip out, repeat steps a-d.
e. If the GFCI fails to trip within 4 to 7 mA, proceed no further, place a caution label
over the outlet, indicate faulty GFCI, and call to have it repaired.
D. Placing an IPRT Test Sticker
If the outlet passes all the above tests, place an IPRT GFCI test sticker, on the outlet cover as indicated in section VII. D.
IX. Bibliography
(1) National Electrical Code, (1993). sections 210-8
(2) National Electrical Code Handbook, (1993). sections 210-8
(3) Department of Energy, Electrical Safety Guidelines, (1993, May)., Sections 8.2.2, 8.4.1
(4) Sandia National Laboratories, Electrical Safety Manual, (March 4, 1994).
(5) Occupational Safety & Heath Standards, 29 CFR 1926.404(b)(1)(ii)
Last updated November 15, 2002
Return to: